Diagnostic system
7.3 Faults
Bit 10
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 11
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bits 12-31
-
7.3.3

Mode Control

Bit 0
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bits 1-31
-
118
DCP of incorrect type was connected
Fault
Hardware configuration of ESS IF PLC
Shutdown routine 3
Warm restart of ESS IF PLC
The device type selected at input inDCPType and the physically connected device
type are not compatible or approved
Check the device class of all connected SINAMICS DCPs
DCP with incorrect FW version was connected
Fault
Hardware configuration of ESS IF PLC
Shutdown routine 3
Warm restart of ESS IF PLC
The firmware versions of the individually connected SINAMICS DCPs vary
A device with a firmware version which is out of date has been connected
Check the firmware of all the connected SINAMICS DCPs and restart the ESS PLC
Spare
-
Default Operation Mode Invalid; Check parametrization
Fault
Mode configuration
Shutdown routine 3
Warm restart of ESS IF PLC
Incorrect parameterization of input inDefaultOperationMode[X] (Page 49)
Check the input inDefaultOperationMode[X] (Page 49)
Spare
-