Diagnostic system
7.3 Faults
Bit 11
Cause
Remedy
Bit 12
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 13
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 14
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 15
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 16
Message class
Component
Response
122
External CAT-0 Stop detected
External emergency stop detected
Clarify the cause and acknowledge the fault provided no safety hazard exists
Stop ESS: Internal Shutdown
Fault
Internal SIMOCRANE ESSM Vx.x
Shutdown routine 2
Acknowledge
Internal stop triggered
Clarify the cause (see following faults) and acknowledge the fault
Start inhibited: No unit selected for startup
Fault
Internal SIMOCRANE ESSM Vx.x
Shutdown routine 2
Acknowledge
No selected unit detected on start command
Select at least one unit for startup
Start inhibited: At least one selected unit is disconnected
Fault
Internal SIMOCRANE ESSM Vx.x
Shutdown routine 2
Acknowledge
At least one electrically isolated unit detected on start command
Deselect the faulted unit
Start inhibited: Main breaker not closed
Fault
Internal SIMOCRANE ESSM Vx.x
Shutdown routine 2
Acknowledge
Main battery breaker open on start command
Close the main battery breaker before starting up the ESS
Internal CAT-0 Stop detected
Fault
Internal SIMOCRANE ESSM Vx.x
Shutdown routine 3
SIMOCRANE Energy Storage System Management V01.01