Bit 3
Response
Acknowledgement
Cause
Remedy
Bit 4
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bit 5
Message class
Component
Response
Acknowledgement
Cause
Remedy
Bits 6-31
-
7.3.13
Unit 8
Bit 0
Message class
Component
Response
Acknowledgement
SIMOCRANE Energy Storage System Management V01.01
Operating Instructions, 04/2023, A5E51573536B AE
Unit Line contactor failure
Shutdown routine 3
ETechAcknowledge
Unit 7 has detected a fault at the bypass contactor
Defective bypass contactor
Clarify the cause
Replace the contactor if necessary
Unit Precharge contactor failure
Fault
Internal SIMOCRANE ESSM Vx.x
Shutdown routine 3
ETechAcknowledge
Unit 7 has detected a fault at the precharge contactor
Defective precharge contactor
Clarify the cause
Replace the contactor if necessary
Unit Disconnected while running
Fault
Internal SIMOCRANE ESSM Vx.x
Shutdown routine 3
ETechAcknowledge
Unit 7 was disconnected from the line supply during operation
Fuse tripped
Clarify the cause
Replace the fuse links if necessary
Spare
-
Unit CAT-0 Stop
Fault
Internal ESSM Vx.x
Shutdown routine 3
ETechAcknowledge
Diagnostic system
7.3 Faults
137