Cable routing for connecting to the supply infeed
1. Feed the infeed cable into the cabinet from the bottom.
2. Connect the PE cable to the grounding bar.
3. Route the cable up through the cabinet to the line connections -X1 (-U1/-L1, -V1/-L2,
-W1/-L3).
4. Connect the cable to the connections.
Cabinet Modules liquid cooled
Manual, 10/2015, A5E37067587A
Electrical installation
4.5 Connections
95