Commissioning the cooling circuit
5.3 Filling the internal deionized water circuit
Danger of injury caused by spray water
The coolant is harmful to eyes and skin and can damage surfaces.
If the air escapes intermittently, coolant spray can come into contact with your skin or eyes.
• Therefore, use appropriate protective clothing for all work on the drive. However, if your
• Please refer to the EU safety data sheet of the coolant manufacturer.
5.3.1.4

Venting the heatsinks of the SINAMICS power units

Danger of injury caused by spray water
The coolant is harmful to eyes and skin and can damage surfaces.
If the air escapes intermittently, coolant spray can come into contact with your skin or eyes.
• Therefore, use appropriate protective clothing for all work on the drive. However, if your
• Please refer to the EU safety data sheet of the coolant manufacturer.
In some devices, the cooling circuit has to be vented when it is being filled, depending on the
device type and the frame size.
● It is not necessary to vent the heat sinks on Active Interface Modules, frame size JXL, on
Active Line Modules, frame size GXL and on Motor Modules, frame sizes FXL and GXL
before they are filled for the first time.
● The heat sinks on Basic Line Modules, frame sizes FBL, GBL, on Active Line Modules,
frame sizes HXL, JXL and on Motor Modules, frames sizes HXL, JXL must be vented
before they are filled for the first time.
– For this purpose, the devices are fitted with a vent valve at the top and a vent hose at
– A stopper is inserted in the lower end of the vent hose at the factory. This must be
124
CAUTION
eyes or skin do come into contact with coolant, rinse the affected area thoroughly with
tap water as soon as possible. If coolant has escaped, remove the liquid from the
affected surfaces.
CAUTION
eyes or skin do come into contact with coolant, rinse the affected area thoroughly with
tap water as soon as possible. If coolant has escaped, remove the liquid from the
affected surfaces.
the bottom. The air and/or coolant can be bled out of the device via this hose and
collected underneath so that it cannot leak into the module.
removed before the heat sink is vented and inserted again afterwards.