2. This paragraph explains how to connect the connector conversion adapter to the main unit.
The FX
-40MT/ES is used as the main unit in this example.
3G
1
Remove the top cover (A in the right figure)
and peripheral device connector cover (B in
the right figure) from the front face of the main
unit.
Caution
The peripheral device connector cover has the possibility of being
damaged when removed. Please remove by pressing on the
attaching tab (a in the figure to the right).
2
Connect the connector conversion adapter to
the option connector (C in the right figure) as
shown in the right figure, and fix it with provided
M3 tapping screws (D in the right figure).
• Tightening torque : 0.3 to 0.6 N•m
3
Fix the connector conversion adapter (E in the
right figure) with provided M3 tapping screws
(D in the right figure) to the main unit.
• Tightening torque : 0.3 to 0.6 N•m
118
8.6 Connecting Methods for Main Unit and Extension Devices
D
8 Installation In Enclosure
A
B
a
D
C
E