2. INSTALLATION PRECAUTIONS
Make sure to cut off all phases of the power supply externally before attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
Use the product within the generic environment specifications described in section 4.1 of this manual.
Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas (salt air, Cl
SO
or NO
), flammable gas, vibration or impacts, or expose it to high temperature, condensation, or rain and wind.
2
2
If the product is used in such conditions, electric shock, fire, malfunctions, deterioration or damage may occur.
Do not touch the conductive parts of the product directly.
Doing so may cause device failures or malfunctions.
Install the product securely using a DIN rail or mounting screws.
Terminal block
Main unit, FX
Series I/O extension unit/block, FX
2N
function block, and special adapter
Install the product on a flat surface.
If the mounting surface is rough, undue force will be applied to the PC board, thereby causing nonconformities.
Make sure to affix the expansion board with tapping screws.
Tightening torque should follow the specifications in the manual.
If the screws are tightened outside of the specified torque range, poor connections may cause malfunctions.
When drilling screw holes or wiring, make sure that cutting and wiring debris do not enter the ventilation slits of the
PLC.
Failure to do so may cause fire, equipment failures or malfunctions.
Be sure to remove the dust proof sheet from the PLC's ventilation port when installation work is completed.
Failure to do so may cause fire, equipment failures or malfunctions.
Connect the extension cables, peripheral device cables, input/output cables and battery connecting cable securely
to their designated connectors.
Loose connections may cause malfunctions.
Connect the display module, memory cassette, and expansion board securely to their designated connectors.
Loose connections may cause malfunctions.
Turn off the power to the PLC before attaching or detaching the following devices.
Failure to do so may cause device failures or malfunctions.
-
Peripheral devices, display modules, expansion boards and special adapters
-
Extension units/blocks and FX Series terminal blocks
-
Battery and memory cassette
Connect the memory cassette securely to the appropriate connector.
Loose connections may cause malfunctions.
Installing the cassette in a raised or tilted posture can also cause malfunctions.
3. WIRING PRECAUTIONS
Make sure to cut off all phases of the power supply externally before attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
Make sure to attach the terminal cover, offered as an accessory, before turning on the power or initiating operation
after installation or wiring work.
Failure to do so may cause electric shock.
The temperature rating of the cable should be 80 C or more.
Safety Precautions
(Read these precautions before use.)
/FX
Series special
2N
3U
(2)
, H
S,
2
2
DIN rail only
DIN rail or direct mounting
Reference
99
356
Reference
100
357
Reference
100
122
140
173
187
226
248
357

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents