Mitsubishi Electric MELSEC-F FX3G Series User Manual page 223

Hide thumbs Also See for MELSEC-F FX3G Series:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3G
User's Manual - Hardware Edition
PLC
Error
operation
code
at error
occurrence
PLC hardware error [M8061(D8061)]
Stops
6107
System configuration error
operation
PLC/PP communication error (D8062)
0000
No error
6201
Parity, overrun or framing error
6202
Communication character error
Continues
6203
Communication data sum check error
operation
6204
Data format error
6205
Command error
Serial communication error 1 [M8063(D8063)]
0000
No error
6301
Parity, overrun or framing error
6302
Communication character error
6303
Communication data sum check error
6304
Communication data format error
6305
Command error
6306
Communication time-out detected
6307
Modem initialization error
Continues
6308
N:N network parameter error
operation
6309
N:N Network setting error
6312
Parallel link character error
6313
Parallel link sum error
6314
Parallel link format error
6320
Inverter communication error
6321
MODBUS communication error
6340
Special adapter connection error
Parameter error [M8064(D8064)]
0000
No error
6401
Program sum check error
6402
Memory capacity setting error
6403
Latched device area setting error
6404
Comment area setting error
6405
File register area setting error
Special unit (BFM) initial value setting, positioning instruction
6406
setting sum check error
Special unit (BFM) initial value setting, positioning instruction
6407
Stops
setting error
operation
6409
Other setting error
6420
Special parameter sum check error
6421
Special parameters setting error
14 Test Operation, Adjustment, Maintenance and Troubleshooting
14.6 Judgment by Error Codes and Representation of Error Codes
Contents of error
Action
Check the number of the connected special function blocks.
For certain special function blocks, the connectable number is
limited.
Check the cable connection between the programming panel
(PP) / programming device and the PLC. This error may occur
when a cable is disconnected and reconnected during PLC
monitoring.
Ethernet
communication,
computer link and programming:
Ensure the parameters are correctly set according to their
applications.
N:N network, parallel link, MODBUS communication, etc.:
Check programs according to applications.
Remote maintenance:
Ensure modem power is ON and check the settings of the
AT commands.
Wiring:
Check the communication cables for correct wiring.
Check connection of the special adapter.
STOP the PLC, and correctly set the parameters.
STOP the PLC, and correctly set the special parameters.
Set special parameters correctly, turn OFF the power, and
then turn ON the power.
Check the contents of the special parameter error code
(D8489), confirm troubleshooting for special adapters/
special blocks, and set special parameters correctly.
Set special parameters correctly, turn OFF the power, and
then turn ON the power.
11
12
13
14
inverter
communication,
15
16
17
18
19
20
217