(22) Alarm No.
[Details] The position tracking error during orientation exceeded the specified value (excessive
error width setting value).
• Excessive error width setting value
During orientation (SP102: OODR): Standard value 32767 (32767 pulses)
During spindle synchronization (SP186: SODR): Standard value 32767 (32767 pulses)
During synchronous tap (SP218: TODR): Standard value 32767 (32767 pulses)
Investigation items
1 Investigate
repeatability.
2 If the alarm occurs
during encoder
orientation, check the
spindle parameter
(SP097: SPEC0) bit5
setting value.
3 Check the spindle
parameter (SP001:
PGM, SP002: PGE,
P006: CSP) setting
values.
4 Jiggle the position and
speed detector
connectors (spindle
drive unit side and
position and speed
detector side) to see
whether they are
coming loose.
5 Turn the power OFF,
and check the position
and speed detector
cable connection with
a tester.
6 Check the speed
detector waveform.
7 If the alarm occurs
during spindle
synchronization, check
the spindle parameter
(SP177: SPECS) bit 5
setting value.
11. Troubleshooting
52 : EXCESSIVE ERROR
Investigation results
The alarm occurs during orientation.
The alarm occurs during spindle
synchronization.
The alarm occurs during
synchronous tap.
The trouble is eliminated by
changing the bit5 setting value.
The trouble is not eliminated by
changing the bit5 setting value.
The trouble is eliminated by raising
the PGM and PGE values 2-fold, or
by halving the CSP value.
The trouble is not eliminated by
changing the values as shown
above.
Connector came (was coming) loose. Install correctly.
Connectors are normal.
The connection is faulty, or there is a
broken wire.
The connection is normal.
The waveform is incorrect.
The waveform is correct.
The trouble is eliminated by
changing the bit5 setting value.
The trouble is not eliminated by
changing the bit5 setting value.
Investigate item 2, and carry out the
appropriate measures.
Investigate item 7, and carry out the
appropriate measures.
Investigate item 11, and carry out the
appropriate measures.
Change the bit5 setting value.
Return bit5 to the original setting
value. Investigate item 3, and carry
out the appropriate measures.
Change the setting value.
Investigate item 4, and carry out the
appropriate measures.
Investigate item 5, and carry out the
appropriate measures.
Replace the detector cable. Correctly
connect the cable.
Investigate item 6, and carry out the
appropriate measures.
Adjust the waveform so it is correct.
Or, replace the detector.
Replace the unit or detector.
Change the bit5 setting value.
Return bit5 to the original setting
value. Investigate item 8, and carry
out the appropriate measures.