● R-UNIT-5 (For 11kW high frequency)
Embedded installation (outer heat radiating section)
3-ø6 hole
Ceiling
Ground
255
Installation hole dimensions for embedded installation
Note 1: The ventilation area is approx. 100 × 120.
Note 2: Attach packing to the flange section.
Note 3: Do not wire or arrange other devices in front of the section marked with a * as extremely hot wind will be blown out.
Note 4: For the installation direction of this resistor, the "Ceiling" is the top and "Ground" is the bottom.
Note 5: Touching the resistor when it is hot could lead to burns. Always install a protective cover or consider the installation site so
that workers will not touch the unit.
Note 6: The resistor's heating value will differ according to the acceleration/deceleration frequency, speed being used and the load
2
GD
conditions, etc. However, install the resistor so that the hot wind is always exhausted to outside the panel.
● Example of resistor installation
Example 1.
To place cooling section on inner side
of distribution panel.
Distribution panel
Inside panel
Cooling
section
2. Specifications
Hot wind discharge
Suction
160
6-M5 x 0.8 screw
Punched
hole
Outside panel
Exhaust
Protective cover
Suction
2 − 20
Terminal layout
(Grounding terminal)
Terminal screw size:
M4 x 0.7 screw
Applicable crimp terminal:
Bare round terminal up to 5.5-4
Example 2.
To place cooling section on outer side
of distribution panel.
Distribution panel
Outside panel
Exhaust
Inside panel
Cooling
section
Suction
Conventional
grounding
terminal
position
Protective cover