Mitsubishi Electric MDS-B-SPJ2 Series Specification Manual page 60

Ac spindle drive unit
Table of Contents

Advertisement

5.2.2 Signal names and applications of the main circuit terminal block
and control circuit terminal block
Terminal
name
Main circuit power
L1•L2•L3
Control circuit power
L11•L12
Regenerative resistor
P•C
connection
Main circuit standard
(N)
potential
Spindle motor output
U•V•W
PE
Ground
5. Connections
Signal name
Main circuit power input terminal
Connect to a 3-phase 200 to 230VAC, 50/60Hz power
supply.
Control circuit power input terminal
Connect to a single-phase 200 to 230VAC, 50/60Hz power
supply.
Connect so the power phase of L11 is the same as L1, and
that of L21 is the same as L2.
Failure to observe this will may result in failure.
Regenerative resistor connection terminal
Wire the regenerative resistor between P and C.
This is normally not used.
(This is the standard potential of the main circuit DC voltage.)
Spindle motor power output terminal
Connect to the spindle motor power terminal (U, V, W).
Grounding terminal
Ground by connecting to the spindle motor grounding
terminal.
Caution Do not connect anything to this terminal unless
specifically instructed by Mitsubishi. Failure to
observe this could result in electric shocks or
spindle amplifier damage.
5 − 5
Details