Mitsubishi Electric MELSEC iQ-R Series User Manual page 106

System recorder user's manual (application)
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Recording status area (Un\G1500 to 3199)
The recording status can be checked.
Buffer memory name
Recording status 1
6 RECORDER MODULE (DETAILED SPECIFICATIONS)
104
6.4 Buffer Memory
Address
In recording operation
Un\G1501
*2
Recording start error
Un\G1502
*2
Recording start error cause
Un\G1503
File saving trigger monitor
Un\G1504
Recording files saving
Un\G1505
Data sampling
Un\G1506
Description
The operating status of the recording function is stored. (Page 40
Operating status)
0: Stopped
1: Operating
'1' (operating) is stored when the recording function starts running after
starting the function.
'0' (stopped) is stored when stopping the operation of the recording
*1
function
or a module stop error occurs.
Whether an error occurred when the recording function started running is
stored.
0: No error
1: Error exists
'1' (error exists) is stored if the recording function cannot start running after
starting the function.
'0' (no error) is stored when the operating status switches to 'preparing' after
starting the recording function. (It is initialized to '0' (no error).)
The code of an error that occurred when the recording function started
running is stored.
0: No error
Values other than 0: Error code
If an error occurs, the error code is stored.
'0' (no error) is stored when the operating status switches to 'preparing' after
starting the recording function. (It is initialized to '0' (no error).)
Whether a file saving trigger is satisfied is stored.
0: Unsatisfied
1: Satisfied
'1' (satisfied) is stored from when a file saving trigger is satisfied to when a
file is saved.
When '1' (satisfied) is stored, recording startup triggers and file saving
triggers are disabled.
Whether a recording file is being saved is stored.
0: Not saving
1: Saving
'1' (saving) is stored when starting to save a recording file.
'0' (not saving) is stored when the file saving is completed.
Whether devices and labels are being sampled and accumulated is stored.
0: Not sampling
1: Sampling
■When selecting "File Saving Trigger Only" for the recording method
• '1' (sampling) is stored when the recording function starts running ('1'
(operating) is stored in 'In recording operation' (Un\G1501)) after starting
the function.
• '0' (not sampling) is stored when starting to save a recording file, and '1'
(sampling) is stored after the file saving is completed.
• '0' (not sampling) is stored when stopping the operation of the recording
function or a module stop error occurs.
■When selecting "Recording Startup Trigger + File Saving Trigger" for the
recording method
• '1' (sampling) is stored when a recording startup trigger is satisfied, and '0'
(not sampling) is stored after devices and labels for a saving period are
accumulated.
• When '1' (sampling) is stored, data accumulation stops and '0' (not
sampling) is stored if the capacity of accumulated data exceeds that of the
recording buffer. (Page 38 Recording buffer)
• '0' (not sampling) is stored when stopping the operation of the recording
function or a module stop error occurs.

Advertisement