5
TROUBLESHOOTING
This chapter explains the errors which may occur in System Recorder and the troubleshooting.
5.1

Recording Function

This section shows the troubleshooting on the recording function.
Troubleshooting on starting the recording function
Symptom
Check point
Unable to start the recording
Is a recording setting for which the recording function starts
function.
written?
Is a CPU module in the RUN state?
Are programs and parameters when setting a recording
setting written to a CPU module?
Are devices and labels that do not exist in the CPU parameter
and modules that are not mounted specified in the device/
label sampling setting in the recording setting?
(Page 56 Device/Label Sampling Setting)
Does the sampling size of a recording setting (total size of
devices and labels specified in the device/label sampling
setting) exceed the capacity of the buffer area for data
sampling in the CPU parameter?
(Page 56 Device/Label Sampling Setting, Page 48 Buffer
area setting for data sampling)
Is the buffer capacity of a recording setting for which the
recording function starts set in the recording buffer setting in
the module parameter (recorder module)?
(Page 51 Recording buffer setting)
Does a program run properly when the device/label batch
specification is enabled in the device/label sampling setting in
the recording setting? (Is a program accessing an unmounted
module running?)
(Page 56 Device/Label Sampling Setting)
Is a condition of a device, which is specified as a recording
startup trigger in a recording setting for which the recording
function starts, satisfied when selecting "Recording Startup
Trigger + File Saving Trigger" for "Recording Method" in the
saving period setting?
(Page 55 For selecting "Recording Startup Trigger + File
Saving Trigger" for "Recording Method", Page 19 Recording
startup trigger)
Is a condition of a device, which is specified as a recording
startup trigger in a recording setting for which the recording
function starts, satisfied while the recording startup trigger is
enabled when selecting "Recording Startup Trigger + File
Saving Trigger" for "Recording Method" in the saving period
setting?
(Page 55 For selecting "Recording Startup Trigger + File
Saving Trigger" for "Recording Method", Page 19 Recording
startup trigger)
Unable to restart the
Is the operating status of the recording function 'saving'?
recording function.
Corrective action
• Write a recording setting for which the recording function
starts.
• Switch the CPU module to the RUN state.
• Write the programs and parameters to the CPU module.
• Review the recording setting.
• Review the recording setting.
• Review the buffer area setting for data sampling in the CPU
parameter.
• Review the recording buffer setting in the module parameter
(recorder module).
• Check the mounted module.
• Review the program accessing an unmounted module.
• Satisfy the condition of the device.
• Satisfy the condition of the device.
• Wait for a recording file to be saved.