Mitsubishi Electric MELSEC iQ-R Series User Manual page 107

System recorder user's manual (application)
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Buffer memory name
Recording status 1
Recording buffer storing
*2
status
Recording files saving
completion
Recording files saving error
Recording files saving
completion code
Recording File Saving
*2
Count
Recording files saving
*2
progress
Address
Un\G1507
Un\G1508
*2
*2
Un\G1509
Un\G1510
*2
Un\G1511
Un\G1514
Description
Whether data in a sampled device and label is accumulated in the recording
buffer is stored.
0: No data
1: Data exists
'1' (data exists) is stored when a device and label are sampled and data is
accumulated in the recording buffer.
'0' (no data) is stored when starting to save a recording file.
When a recording startup trigger is satisfied, accumulated data is discarded
and '0' (no data) is stored.
'0' (no data) is stored when the operating status switches to 'operating' after
starting the recording function. (It is initialized to '0' (no data).)
Whether saving a recording file is completed is stored.
0: Not completed
1: Completed
'1' (completed) is stored when saving a recording file is completed.
'0' (not completed) is stored when a file saving trigger is satisfied.
'0' (not completed) is stored when the operating status switches to 'operating'
after starting the recording function. (It is initialized to '0' (not completed).)
Whether an error occurred when saving a recording file is stored.
0: No error
1: Error exists
'1' (error exists) is stored if a recording file fails to be saved.
'0' (no error) is stored when a file saving trigger is satisfied.
'0' (no error) is stored when the operating status switches to 'operating' after
starting the recording function. (It is initialized to '0' (no error).)
The code of an error occurred when saving a recording file is stored.
0: No error
Values other than 0: File saving failed (error code)
An error code is stored if a file fails to be saved.
'0' (no error) is stored when a file saving trigger is satisfied.
'0' (no error) is stored when the operating status switches to 'operating' after
starting the recording function. (It is initialized to '0' (no error).)
The number of times that recording files have been saved (both successful
and failed) is stored.
It is initialized to '0' when the operating status switches to 'operating' after
turning the power ON or resetting a CPU module and starting the recording
function.
In addition, it is initialized to '0' when the operating status switches to
'operating' after adding or changing a recording setting and starting the
recording function.
When it reaches 65535 times, it returns to 1 and continues counting.
If it is reset, '0' is stored.
(Value to be stored: 0 to 65535)
The progress rate (%) of saving a recording file is stored.
It is initialized to '0' when the operating status switches to 'operating' after a
file saving trigger is satisfied or starting the recording function.
(Value to be stored: 0 to 100%)
6 RECORDER MODULE (DETAILED SPECIFICATIONS)
105
6.4 Buffer Memory
6