■When the auto tuning is started with the temperature process value (PV) that is within the
stable judgment width (1 ()) after the mode has shifted from the setting mode to the
operation mode
Until the temperature process value (PV) goes outside the stable judgment width (1 ()), the data measured after the mode
has been shifted to the operation mode ('Setting/operation mode command' (Y1) is turned from OFF to ON) can be used.
Thus, the simultaneous temperature rise parameter can be calculated by the auto tuning.
Temperature
process value
(PV)
Self-tuning start
'Setting/operation mode status'
(X1)
OFF
'CH1 Auto tuning status'
(X4)
OFF
'CH1 Auto tuning command'
(Y4)
OFF
CH1 PID auto-correction status
(Un\G411, b0)
OFF
CH1 Simultaneous temperature
rise parameter correction status
OFF
(Un\G411, b1)
CH1 Simultaneous temperature
rise parameter error status
OFF
(Un\G411, b9)
CH1 Self-tuning error
(Un\G411, b10)
OFF
CH1 AT simultaneous
temperature rise parameter
calculation completion
OFF
(Un\G413, b0)
CH1 AT simultaneous
temperature rise parameter
calculation error status
OFF
(Un\G413, b1)
Maximum gradient
Dead time
Simultaneous
temperature rise
AT start
ON
ON
ON
Auto tuning waveform
Time
ON
1.32 Simultaneous Temperature Rise Function
1
'CH1 Self-tuning flag'
(Un\G411)
'CH1 AT simultaneous
temperature rise
parameter calculation
flag' (Un\G413)
1 FUNCTIONS