Mitsubishi Electric MELSEC iQ-R Series User Manual page 307

Temperature control module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

CH1 Simultaneous temperature rise AT mode selection
Select an auto tuning mode.
For details on the auto tuning function, refer to the following:
Page 38 Auto Tuning Function
For details on the simultaneous temperature rise function, refer to the following:
Page 100 Simultaneous Temperature Rise Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Simultaneous temperature rise AT mode selection
CH Simultaneous temperature rise AT mode selection (in the Q compatible
mode)
■Setting range
• 0: Select normal auto tuning
• 1: Select simultaneous temperature rise AT
■Default value
The default value is Select normal auto tuning (0).
• This setting can be used with the setting of 'CH1 Auto tuning mode selection' (Un\G543).
• When this setting is changed during the auto tuning, the setting will be enabled in the next auto tuning.
CH1
CH2
556
756
733
749
Appendix 3 Buffer Memory Areas
CH3
CH4
956
1156
765
781
APPX