CH1 Simultaneous temperature rise AT mode selection
Select an auto tuning mode.
For details on the auto tuning function, refer to the following:
Page 38 Auto Tuning Function
For details on the simultaneous temperature rise function, refer to the following:
Page 100 Simultaneous Temperature Rise Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Simultaneous temperature rise AT mode selection
CH Simultaneous temperature rise AT mode selection (in the Q compatible
mode)
■Setting range
• 0: Select normal auto tuning
• 1: Select simultaneous temperature rise AT
■Default value
The default value is Select normal auto tuning (0).
• This setting can be used with the setting of 'CH1 Auto tuning mode selection' (Un\G543).
• When this setting is changed during the auto tuning, the setting will be enabled in the next auto tuning.
CH1
CH2
556
756
733
749
Appendix 3 Buffer Memory Areas
CH3
CH4
956
1156
765
781
APPX
305
A