Mitsubishi Electric MELSEC iQ-R Series User Manual page 323

Temperature control module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

CT1 CT selection
Select the current sensor (CT) to be connected to CT1 in the R mode.
■Setting range
• 0: CTL-12L-8 (0.0 to 100.0A)
• 1: CTL-6-P-H/CTL-6-S-H (0.00 to 20.00A)
• 2: CTL-12-S36-10/CTL-12-S56-10 (0.0 to 100.0A)
• 3: CT ratio setting (0.0 to 100.0A)
■Correspondence between each CT input terminal and buffer memory address
CT input terminal
CT1
CT2
CT3
CT4
CT5
CT6
CT7
CT8
■Setting current sensors (CT) and buffer memory areas
Set the following buffer memory areas as follows according to the specifications of the current sensor (CT) to be used:
Current sensor (CT) to be used
Products of
CTL-12L-8
U.R.D.Co., LTD.
CTL-6-P-H
www.u-rd.com
CTL-6-S-H
CTL-12-S36-10
CTL-12-S56-10
Other current sensors (CT)
• When using the CTL-12-S36-8 current sensor (CT), set CTL-12L-8 (0.0 to 100.0A) (0).
• When using the CTL-6-P current sensor (CT), set CTL-6-P-H/CTL-6-S-H (0.00 to 20.00A) (1).
■Enabling the settings
Turn ON and OFF 'Setting change command' (YB) in the setting mode ('Setting/operation mode status' (X1): OFF) to enable
the settings.
■Occurrence of a write data error
When a value out of the setting value is set, a write data error (error code: 1950H) occurs. 'Error flag' (X2) turns ON and the
error code is stored in 'Latest error code' (Un\G0).
■Default value
The default value is CTL-12L-8 (0.0 to 100.0A) (0).
'CT1 CT selection' (Un\G2046)
CTL-12L-8 (0.0 to 100.0A) (0)
CTL-6-P-H/CTL-6-S-H (0.00 to 20.00A)
(1)
CTL-6-P-H/CTL-6-S-H (0.00 to 20.00A)
(1)
CTL-12-S36-10/CTL-12-S56-10 (0.0 to
100.0A) (2)
CTL-12-S36-10/CTL-12-S56-10 (0.0 to
100.0A) (2)
CT ratio setting (0.0 to 100.0A) (3)
Buffer memory address
2046
2047
2048
2049
2050
2051
2052
2053
'CT1 CT ratio setting' (Un\G2062)
Setting not required
Setting not required
Setting not required
Setting not required
Setting not required
Set the number of second-winding (turns)
depending on the specifications of the
current sensor (CT) used.
Appendix 3 Buffer Memory Areas
Remarks
A
Current sensors (CT)
whose number of
secondwinding (turns) is
600 to 9999 can be used.
APPX
321

Advertisement

Table of Contents
loading

This manual is also suitable for:

R60tctrt2tt2R60tcrt4R60tctrt2tt2bwR60tcrt4bw

Table of Contents