CT1 Reference heater current value
Set the reference value of 'CT1 Heater current process value' (Un\G2030) for when the heater is turned ON. ( Page 319
CT1 Heater current process value)
■Correspondence between each CT input terminal and buffer memory address
CT input terminal
CT1
CT2
CT3
CT4
CT5
CT6
CT7
CT8
■Setting range
The setting range is within the heater current range of the current sensor set in 'CT1 CT selection' (Un\G2046).
'CT1 CT selection' (Un\G2046)
• CTL-12-S36-8 (0.0 to 100.0A) (0)
• CTL-12-S36-10/CTL-12-S56-10 (2)
• CT ratio setting (0.0 to 100.0A) (3)
CTL-6-P(-H) (0.00 to 20.00A) (1)
■Default value
The default value is 0 (0.0A).
CT1 CT ratio setting
Set the number of second-winding (turns) of the current sensor (CT) to be connected. This setting is enabled only when 'CT1
CT selection' (Un\G2046) has been set to CT ratio setting (0.0 to 100.0A) (3). (In the Q compatible mode, this setting is
enabled only when 'CT1 CT selection' (Un\G2046) has been set to CT ratio setting (0.0 to 100.0A) (2).) ( Page 321 CT1
CT selection, Page 322 CT1 CT selection [Q compatible mode])
■Correspondence between each CT input terminal and buffer memory address
CT input terminal
CT1
CT2
CT3
CT4
CT5
CT6
CT7
CT8
■Setting range
The setting range is 600 to 9999.
■Default value
The default value is 800.
APPX
324
Appendix 3 Buffer Memory Areas
Buffer memory address
In the R mode
2054
2055
2056
2057
2058
2059
2060
2061
Setting range
0 to 1000 (0.0 to 100.0A)
0 to 2000 (0.00 to 20.00A)
Buffer memory address
In the R mode
2062
2063
2064
2065
2066
2067
2068
2069
In the Q compatible mode
280
281
282
283
284
285
286
287
In the Q compatible mode
288
289
290
291
292
293
294
295