CH1 Simultaneous temperature rise gradient data
Set simultaneous temperature rise gradient data (temperature rise per minute). For details on the simultaneous temperature
rise function, refer to the following:
Page 100 Simultaneous Temperature Rise Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Simultaneous temperature rise gradient data
CH Simultaneous temperature rise gradient data (in the Q compatible mode)
■Setting range
The setting range is 0 to the full scale of the input range.
■Default value
The default value is 0.
This setting can be set manually and calculated automatically. Automatic calculation is executed when the
simultaneous temperature rise AT (auto tuning) or self-tuning (when the calculation of the simultaneous
temperature rise parameter has been set) is completed successfully.
CH1 Simultaneous temperature rise dead time
Set the simultaneous temperature rise dead time (time taken for the temperature to start rising after the output is turned ON).
For details on the simultaneous temperature rise function, refer to the following:
Page 100 Simultaneous Temperature Rise Function
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Simultaneous temperature rise dead time
CH Simultaneous temperature rise dead time (in the Q compatible mode)
■Setting range
The setting range is 0 to 3600 (s).
■Default value
The default value is 0.
This setting can be set manually and calculated automatically. Automatic calculation is executed when the
simultaneous temperature rise AT (auto tuning) or self-tuning (when the calculation of the simultaneous
temperature rise parameter has been set) is completed successfully.
APPX
304
Appendix 3 Buffer Memory Areas