CH1 Input range
Select corresponding setting values from the temperature sensors used with the temperature control module, temperature
measuring range, temperature unit to be output (Celsius ()/Fahrenheit ()/digit) and resolution (1/0.1).
For inputs from other analog modules (such as an A/D converter module) also, set these values.
Ex.
When selecting the following thermocouple:
• Thermocouple type: R
• Temperature measuring range: 0 to 1700
• Resolution: 1
Set 'CH1 Input range' (Un\G501) to 1.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory area name
CH Input range
CH Input range (in the Q compatible mode)
■Setting value and type of thermocouple
The following table lists the setting values of 'CH1 Input range' (Un\G501) and the corresponding thermocouple types. The
relation between each temperature unit and setting value is also shown as follows:
• Temperature unit
Setting of 'CH1 Input range' (Un\G501)
1 to 99
100 to 199
200 to 299
• Setting value
Thermocouple type
R
K
APPX
254
Appendix 3 Buffer Memory Areas
Item
A thermocouple is used.
Other analog modules (such as an A/D converter
module) are used.
Temperature
Celsius (),
measuring
Fahrenheit
range
(), digit
0 to 1700
0 to 3000
0 to 1300
0 to 500
0 to 800
0.0 to 400.0
-200.0 to 400.0
0.0 to 500.0
0.0 to 800.0
-200.0 to 1300.0
0 to 1000
0 to 2400
0.0 to 1000.0
CH1
501
32
Resolu
'CH1 Input
tion
range'
(Un\G501)
1
1
1
105
1
2 (default value)
1
11
1
12
0.1
36
0.1
38
0.1
40
0.1
41
0.1
49
1
100
1
101
0.1
130
CH2
CH3
701
901
64
96
When the output temperature unit is Celsius ()
When the output temperature unit is Fahrenheit
()
When the unit is digit
Automatic setting at input range change
'CH1 Upper limit
'CH1 Lower limit
setting limiter'
setting limiter'
(Un\G511)
(Un\G512)
1700
0
3000
0
1300
0
500
0
800
0
4000
0
4000
-2000
5000
0
8000
0
13000
-2000
1000
0
2400
0
10000
0
CH4
1101
128
*1