11. In the "Load preview" dialog box, specify the options for the loading process.
– "Load Runtime": Selection list for overwriting or keeping the runtime software on the
– "Fit": In this area you define whether the version of individual components should be
– "Runtime start": Selection list that allows you to specify whether the runtime software
– "Runtime values": In this area you define whether the data of tags, alarms and the
– "Reset logs": Selection list for resetting or keeping all logs. If you select "Reset all", the
– "HMI Runtime": This area contains information about runtime and firmware/operating
– "Secure transfer": In this area you determine whether the project is transferred
If a warning with light red text is no longer displayed, the "Download" icon in the left
"Status" column of the "Load preview" dialog is displayed in green and the "Load" button
is activated.
12. Click "Load" to transfer the project to the HMI device.
The project is transferred to the HMI device. If errors or warnings occur during the
transfer, alarms are displayed in the Inspector window under "Info> Download". After the
successful transfer, the alarm "Load finished (errors: 0; warnings: 0)" is displayed.
13. In the Control Panel of the HMI device, select "Service and Commissioning" > "Transfer".
14. Clear the "Enable Transfer" option to protect the HMI device from an unintended transfer.
Result
The project is located on the HMI device and can be started. After the transfer, test the
operating elements and screen changes in the "offline" mode. If all operating elements and
screen changes function correctly, you can switch the HMI device to "online" mode.
Unified Comfort Panels
Operating Instructions, 03/2020, A5E46641217-AA
HMI device.
adjusted if the version of the component in the configuration differs from the version of
the component on the HMI device. If the version on the HMI device is more recent,
you can select "Downgrade", otherwise "Upgrade".
is started on the HMI device after loading or not.
user administration should be retained on the HMI device or not. If the respective
option is selected, the data on the HMI device will be retained. If the respective option
is cleared, then the data on the HMI device will be deleted or overwritten by the data in
the configuration. If you want to update user administration on the HMI device, the
"Keep current user administration data in runtime" option must be cleared.
data of all data logs, alarm logs and context logs are deleted on the HMI device.
system version of the HMI device.
encrypted or not. Additional information is available in the section "Transfer
(Page 103)".
Transferring data
6.5 Transferring a project with WinCC
127