8.2.3 Alarm

8.2.4 History Query

8.2.5 Linkage Control

Issue 06 (2020-05-21)
The system monitors the status of smart cooling products, power distribution, and
environment. If a fault or parameter error occurs, the system generates an alarm in real
time. You can view the alarm cause and solution in the alarm details.
Alarms can be classified into four severities: critical, major, minor, and warning. The
alarm severities can be user-defined.
Active alarms can be filtered by device and alarm severity.
Real-time alarms can be displayed in different colors on the power supply link view of
the app. Alarms can be associated with the alarm beacon and eLight. The color
corresponding to the alarm severity is displayed on the aisle door of the smart module.
Alarm notifications can be sent by email and SMS.
A maximum of 500 concurrent active alarms are supported.
Historical alarm export: You can view the alarms that have been generated in the system.
The historical alarm information includes the device name, alarm name, alarm severity,
alarm generation time, and alarm clearance time.
Performance data statistics: You can view historical data of devices to help analyze data
or problems.
Operation log query: You can view logs of key operations, such as user login, parameter
modification, data export, device upgrade, and access control events.
Data export: You can export historical data of the ECC800-Pro and certain southbound
devices.
Supports the linkage logic of aisle smoke alarms or high temperature alarms. By default,
the skylights are opened by linkage. You can manually configure the linkage to open the
end doors (automatic sliding doors), turn on the aisle lights, and shut down the smart
cooling products.
The aisle smoke sensor alarm cannot trigger the customer's fire extinguishing system. Only dry contact
alarm signals are provided.
The smart cooling product in the aisle can be stopped when the dry contact alarm of the
customer's fire extinguishing system is generated.
Dry contact alarms or signals can be associated with the customer's or external fire
extinguishing system to open the skylight, the door status sensor, and the lighting
system.
You can manually configure linkage policies for monitoring systems inside the smart
module.
Intelligent lighting (motion detection): If a motion within the aisle is detected, the aisle
light turns on. If a motion is no longer detected within 10 minutes (can be set), the aisle
light turns off automatically.