Huawei FusionModule2000 Product Description page 113

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Product Description
Item
Altitude
Table 7-4 Altitude table
Height
Density correction
Air volume correction
Refrigeration volume
correction
Physical Ports
Table 7-5 Physical ports
Item
Refrigerant liquid pipe
Refrigerant gas pipe
Water inlet pipe to the
humidifier
Installation Requirements
When the total load power of servers corresponding to a single smart cooling product is less
than 5 kW or the equipment room airtightness is not satisfactory, the indoor humidity might
be relatively high, which is not a product quality issue. You are advised to install a
dehumidifier in the equipment room in this case.
Issue 06 (2020-05-21)
Specifications
0–1000 m. When the altitude is greater than 1000 meters, the
cooling capacity is derated. The maximum operating altitude is
4000 meters. For the detailed derated data, reference the
7-4.
0
1000
1
0.887
1
0.887
1
0.940
Specifications
Copper pipe, with an outer diameter of 5/8 inch (15.88 mm)
and thickness of 1.0 mm, withstanding a pressure not smaller
than 4.5 MPa, welding
Copper pipe, with an outer diameter of 3/4 inch (19.05 mm)
and thickness of 1.0 mm, withstanding a pressure not smaller
than 4.5 MPa, welding
G 1/2 inch inner screw thread
Copyright © Huawei Technologies Co., Ltd.
7 Temperature Control System
1500
2000
2500
0.835
0.785
0.737
0.835
0.785
0.737
0.909
0.878
0.846
Table
3000
3500
4000
0.692
0.649
0.608
0.692
0.649
0.608
0.815
0.784
0.753
105