FusionModule2000 Smart Modular Data Center
Product Description
Figure 7-16 Low-temperature component
(1) Safety valve
(4) Condensing pressure
control valve
A low-temperature component is mandatory when the outdoor ambient temperature may drop
to –20º C.
Table 7-25 Low-temperature component specifications
Item
Heater power supply
Heater power supply voltage tolerance
Heater power supply frequency
tolerance
Refrigerant
Liquid pipe outer diameter
Gas pipe outer diameter
H x W x D
Issue 06 (2020-05-21)
(2) Connecting to indoor
unit liquid pipe
(5) Connecting to outdoor
unit gas pipe
Copyright © Huawei Technologies Co., Ltd.
7 Temperature Control System
(3) Connecting to outdoor
unit liquid pipe
(6) Connecting to indoor unit
gas pipe
Specifications
220–240 V AC, 1 Ph, 50 Hz or 60 Hz
Rated voltage ± 10%
Rated frequency ± 3 Hz
R410A
5/8 inch (15.88 mm)
7/8 inch (22.22 mm)
632 mm x 944 mm x 507 mm (with package)
470 mm x 828 mm x 300 mm (without package)