5.2.2.4.4 Monitoring Interface Card

The monitoring interface card provides external ports as well as monitoring and control
functions for the MDU. The ports include the ambient temperature and humidity sensor port,
FE port, battery temperature monitoring port, and network management port. MDU functions
include monitoring of the UPS, allowing users to set parameters, command delivery,
information reports, and UPS key information and parameters displayed on the LCD.
Issue 06 (2020-05-21)
Description
Port for monitoring the
bypass input circuit breaker
Port for signal ground
Port for monitoring the
input AC surge protective
device (SPD)
Port for signal ground
The dry contact interface card takes effect only after it is set on the monitoring system. Set the
unused dry contact signal to the unused status.
Set the EPO port to NO or NC as required.
When multiple UPSs are paralleled, all dry contact signals to be used need to connect to each UPS.
Single cables require dual-insulated twisted cables. If the length of a power cable is within 25–50 m,
its cross-sectional area must be 0.5 mm
Only once being set will dry contact signals take effect. Set unused dry contact signals to
the unused state on the LCD.
In a parallel system, ensure that used dry contacts properly connect to each UPS.
Copyright © Huawei Technologies Co., Ltd.
5 Power Supply and Distribution System
Status
Connected: circuit
breaker ON
Disconnected:
circuit breaker
OFF
Connected: SPD
enabled
Disconnected:
SPD disabled
2
2
to 1.5 mm
.
Initial Status
Connected
Connected
52