Advertisement

FusionModule2000 Smart Modular Data Center
Product Description
Table 7-26 Operating environment specifications with water cooling module
Item
Power system
Refrigerant
Heat exchanging
capacity
Temperature range
Humidity range
Storage temperature
Storage humidity
Inlet water
temperature range of
chilled water
Highest operating
temperature of the
shell pass (° C)
Highest operating
temperature of the
tube pass (° C)
IP rating
Altitude
Environment
Dimensions (H x W x
D)
Net weight (kg)
Certification
Issue 06 (2020-05-21)
The water cooling module can be installed in stack mode to maximize the installation
space and reduce the footprint.
The water cooling module uses cooling water for heat exchange to improve the heat
exchange efficiency and improve the energy efficiency of the entire system to 4.0 COP.
Technical Specifications
220 V to 240 V AC 1Ph 50 Hz/60 Hz
R410A
55 kW
4° C to 45° C
5%–90% RH
–40° C to +70° C
5%–95% RH (non-condensing)
10° C to 37° C
125
60
IPX4
0–4000 m (derated when the altitude is greater than 1000 m)
Enclosed indoor environment in which the temperature and
humidity can be controlled within the ranges of 4° C to 45° C and
5% RH to 90% RH respectively. If the indoor installation position
is ventilated, it should be more than 5 km away from the sea or
pollution sources (such as salt lakes, chemical plants, mineral
plants, thermal power plants, and coal mines).
330 mm x 326 mm x 1417 mm
60
CE, RoHS, REACH, WEEE, and Chinese industrial product
manufacture license
Copyright © Huawei Technologies Co., Ltd.
7 Temperature Control System
135