Chapter 4 Maintenance and Inspection

4.1 Daily Inspection

Check the following points during system operation on daily basis.
CAUTION
4
Supplement
・ To keep the system normal and prevent unnecessary troubles, perform the daily inspection,
periodic inspection, and cleanup.
Item
Checking LEDs on
the power supply
Checking FL654A
module LED
indication
Checking I/O unit
input module LED
indication
Checking I/O unit
output module LED
indication
Checking the
switch position of
the FL654A module
24
6F8C1625
Turn off the power if there is smoke or abnormal odor
Otherwise, fire or electric shock may be caused.
Table 8-1 Daily checking items
Check points
Lit when 5V power is normal
On normal operation RUN (green),
FLN (green), LNT (green), I/O (green),
LNK (green), ACT (orange) lit
Lit when the corresponding input
signal is ON
Lit when the output is ON and the
corresponding external load should
operate
RUN/HALT switch: RUN
Node address switches (NA-H, NA-L):
A predetermined node number
Mode setting switch (MODE): All OFF
Corrective measures
・ Check the power supply voltage.
・ Check main power supply connection.
・ Check switch setting and cable connection.
・ Reset the I / O configuration information.
・ Check that the input voltage is within the specified
range.
・ Check that the input terminal block is not loose.
・ Check that the modules are installed securely.
・ Check that the external load voltage is within the
specified range.
・ Check the built-in fuses.
・ Check that the output terminal block is not loose.
・ Check that the modules are installed securely.
Change the switch to the correct position described
in this manual.
Mandatory