9.1.5 Operation Mode Setting
Set the FL654A operation mode from the nV-Tool.
(1) Click on the "Tool" menu in the System View (Station Status) screen to display the menu.
(2) In this menu, click on the "Set Run Mode..." item. The Set Operation Mode screen appears.
(3) Select the desired mode from among RUN, HALT, and Error Reset.
(To perform a "Download" operation from the Module Parameters screen, request a HALT from
this screen and after a write is complete, request a RUN.)
9.1.6 Calendar/Time Setting
FL654A doesn't maintain calendar/time for power supply OFF period. Therefore, correct time
doesn't remain in event log information if it doesn't set it at time when restoring it at power supply
OFF time. An initial value is 0:0:0, January 1, 1999.
■ FL654A's calendar/time setting by nV-Tool
(1) Click on the "Tool" menu in "System View (Station Status)" screen to display the menu.
(2) In this menu, click "Set Time..." item. "Set Time" screen appears.
(3) Click "Set Time" button to write the nV-Tool's current time of day to the FL654A.
If the function of setting calendar/time from the master station is not used, set the time of day
from this screen at the time when the FL654A recovers from power OFF.
Unified Controller nv Series FL-net Remote I/O Station Module FL654A User's Manual
9.1 Maintenance Function
9
79