Allocation Of G2 I/O Module Data To Common Memory - Toshiba FL654A User Manual

Fl-net remote i/o station module
Table of Contents

Advertisement

8.1.2 Allocation of G2 I/O Module Data to Common Memory

When FL654A operates by "TOOL specification", FL654A subordinate's G2 I/O module data is
allocated to FL-net common memory as follows.
(1) Input module data can be allocated freely to FL654A talker area by each input module. FL654A
talker area can be allocated in both area1 and area2 in FL-net common memory.
(2) Output module data can be allocated freely to the areas other than FL654A talker area by each
output module.
Table 8-1 Difference of TOOL specification and AUTO / LOCK specification
Item
Input module data
Allocation
Output module data
Allocation
Send data allocation
area
(Talker block)
Receive data
allocation area
(Listener block)
Area1 block head
address / size
Area2 block head
address / size
Status information of
I/O module and
FL654A healthy counter
AUTO / LOCK specification
Input module data is allocated from
the head of talker block in the former
stuff.
Talker
block
head
address
specified
with
rotary
(TBH,TBL).
Output module data is allocated
from the head of listener block in the
former stuff.
Listener block head address is
specified
with
rotary
(LBH,LBL).
Send data allocation area can set
one consecutive area to either of
FL-net common memory area1 or
area2 at the same time.
Receive data allocation area can set
one consecutive area to either of
common memory area 1 or area 2 at
the same time.
Block head address: 2 word unit
Size: 2 word unit
Block head address: 32 word unit
Size: 32 word unit
It is allocated to first 4 words of send
data allocation area.
Unified Controller nv Series FL-net Remote I/O Station Module FL654A User's Manual
TOOL specification
Input module data can be allocated
freely to FL654A talker area by each
input module.
is
(Talker block setting of nV-Tool is
switch
used.)
Output module data can be allocated
freely to the areas other than FL654A
talker area.
(Talker block setting of nV-Tool is
switch
used.)
Rotary switch (TBH,TBL) is not used.
FL654A talker area becomes send
data allocation area.
One
consecutive
allocation
area
respectively of common memory
area1 and area2.
Rotary switch (LBH,LBL) is not used.
Because data in FL-net common
memory other than FL654A talker
area can be specified for receive
data allocation area.
Block head address: 1 word unit
Size: 1 word unit
Block head address: 1 word unit
Size: 1 word unit
It is allocated to first 4 words of send
data allocation area.
8.1 Outline of Operation