Figure 6-28 Battery copper bar wiring holes (1600 kVA, unit: mm)
● The rated voltage of the SmartLi is 512 V. The voltage is 408 V at the maximum
● If the top cabling component and bottom cabling cabinet are configured, refer
● For a three-phase three-wire model, you do not need to configure the neutral
● In a parallel system, the length and specifications of power cables on each UPS
The cables need to be selected according to the site survey data. The cable
recommendation is for your reference only.
Table 6-2 Recommended power cable cross-sectional areas (900–1200 kVA)
Item
Mains input
Mains input
current (A)
Recomme
nded
cross-
sectional
area
(mm
Issue 05 (2021-10-13)
NO TICE
discharge current.
to the recommended cable specifications in the following table for the mains
input, bypass input, and output.
wires for the mains input, bypass input, and output. In a parallel system, the
neutral wires for the mains input of each UPS must be connected together
using a single 185 mm
should be the same to achieve current equalization in bypass mode. The power
cables include bypass input power cables and UPS output power cables.
900 kVA
1672
L1
5 x 240
L2
5 x 240
L3
5 x 240
2
)
N
5 x 240
PE
2 x 240
Copyright © Huawei Technologies Co., Ltd.
2
90°C-resistant copper flexible cable.
1000 kVA
1858
5 x 240
5 x 240
5 x 240
5 x 240
2 x 240
6 Installation
1100 kVA
1200 kVA
2044
2229
6 x 240
6 x 240
6 x 240
6 x 240
6 x 240
6 x 240
6 x 240
6 x 240
2 x 240
2 x 240