UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
Procedure
Step 1 On the LCD, choose System Info > Settings > Dry Contact Set and set MUE06A
connection to Enable.
----End
7.2 Shutting Down and Powering Off the UPS
Context
If the bypass is normal, the UPS transfers to bypass mode after the inverter is shut
down; if the bypass is abnormal, the UPS supplies no power after the inverter is
shut down. Before shutting down the UPS, ensure that all loads have been shut
down.
Procedure
Step 1 Shut down the inverter.
●
●
If the inverter shuts down and the bypass is normal, the UPS transfers to bypass
mode. The Bypass mode alarm is displayed on the LCD.
Issue 05 (2021-10-13)
NO TE
If MUE06A connection is set to Enable and the backfeed protection card fails to
communicate with the UPS, the system reports a Dry contact board fault alarm.
NO TICE
Shutting down the inverter on the LCD
Choose Common Functions > Inv. OFF. After confirmation, the inverter is
shut down.
NO TE
You can also choose System Info > Maintenance > Inv. OFF to shut down the
inverter.
Shutting down the inverter on the WebUI
Choose Monitoring > UPS System > Running Control, and click Inv. OFF.