UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
Figure 6-55 Connecting a signal cable between the UPS and the SmartLi (only for
SmartLi 2.0)
(1) Monitoring interface unit in the master SmartLi cabinet
----End
6.3.3 Installation in Bottom Cabling Configuration
Cables can be routed from the bottom if the optional bottom cabling cabinet is
configured.
6.3.3.1 Installing Cabinets
Installation on the Floor
Ensure that the installation floor is flat.
Step 1 Determine the cabinet installation positions on the floor based on the holes in the
marking-off template for floor installation.
Issue 05 (2021-10-13)
NO TE
● Do not bind signal cables and power cables together.
● RS485 cables and FE cables must be shielded cables.
● The figure uses the cable connection between the UPS and the SmartLi as an example.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
6 Installation
119