Defining JOG reference frequency,JOG acceleration time and JOG deceleration
time.JOG running process operate according to the direct starting for start-stop operation
way and slow down.
JOG acceleration time is the required time of inverter from 0Hz Accelerating to
Maximum output frequency(F0.07).
JOG deceleration time is the required time of inverter from Maximum output
frequency(F0.07) decelerating to 0Hz.
Code
F8.09
F8.10
F8.11
By means of setting skip frequency, the inverter can keep away from the mechanical
resonance with the load. F8.09 and F8.10 are center value of frequency to be skipped.
Note:
● If F8.11 is 0, the skip function is invalid.
● If both F8.09 and F8.10 are 0, the skip function is invalid no matter what F8.11 is.
● Operation is prohibited within the skip frequency bandwidth, but changes during
acceleration and deceleration are smooth without skip.
The relation between output frequency and reference frequency is shown in following
figure.
Name
Skip frequency 1
Skip frequency 2
Skip frequency amplitude
101
Setting Range
0.00ÿ^F0.07
0 0.00Hz0
0.00ÿ^F0.07
0 0.00Hz0
0.00ÿ^F0.07
0 0.00Hz0