Set F0.16 to be then press the DATA/ENTÿ LED will display"TURN"and flicker.Press
RUN to start the autotuning,and the LED will display"TURN" ,"RUN"light will flicker,motor
begin to run.When"RUN"lights off,that means the autotuning is finished and return to the
stop status.
When flickers"TURN"flickers,pressing PRG/ESC can escape from the parameter
autotune.
During the autotuning, press the STOP/RST will stop the autotune.
Note: Only keypad can control the autotuning. F0.16 will restore to 0
automatically when the autotuning is finished.
2: Static autotuning
When motor static parameter autotune, will not interrupt motor and load.Before the
motor parameter self learning, it is necessary to correct the input parameters of motor
nameplates.Since autotuning will detect the motor stator resistance and rotor resistance
and leakage inductance of the motor.But the mutual inductance and the non-load current
can not be measured.if needed user should input suitable value according to experience.
Code
F0.17
0:No action
1:Restore factory parameters (without motor parameters)
2:Clear fault records
3:Restore all factory parameters (including motor parameters)
This Code will restore to 0 automatically when complete the function operation.
Name
Restore parameters
65
Setting Range
0ÿ^30 00