Appropriate Settings PID,Preset frequency holding time or Preset output switching
thresholds Can avoid the inverter start initial feedback and instruction deviation limits and
make the PID regulator saturation,Can make the closed-loop regulating quickly into a
stable stage and no obvious overshoot or oscillation.
After the PID operation,Frequency accelerates to PID preset frequency according to
ACC/DEC time,and run continuously at the frequency point until the output can not meet
the needs of F9.14 setting PID preset keep conditions, according to the PID output
operation.As shown in the figure below:
Code
F9.16
F9.17
F9.18
PID dormancy:When the system detects the PID feedback value higher than that of
PID frequency thresholds and maintain longer than PID after dormancy detection
time,inverter will start deceleration according to the current set of deceleration
Fig.6-24 PID preset output diagram
Name
Dormancy frequency
Dormancy detection time
Start-up threshold
113
Setting Range
0.00ÿ^300.00
0 0.00Hz0
0~2000S0 10S0
0.0%ÿ^100.0%
0 80.0%0