INSTALLATION
4.1 Environment
Avoid installing the product in the sites with oil mist, metal powder and dust.
Avoid installing the product in the sites with hazardous gas and liquid, and
corrosive, combustible and explosive gas.
Avoid installing the products in salty sites.
Do not install the product in the sites with direct sunlight.
Do not mount the product on the combustible materials, such as wood.
Keep the drilling scraps from falling into the inside of drive during the installation.
Mount the product vertically in the electric control cabinet, mount the cooling fan
or air conditioner to prevent the ambient temperature from rising to above 40 °C.
For the sites with hash environment, it is recommended to mount the drive heat
sink outside the cabinet.
4.2 Mounting Direction and Space
In order not to reduce the drive cooling effect, the drive must be mounted vertically,
and certain space must be maintained, as shown below (1):
Mounting direction and space installation diagram
When installing multiple drives vertically upside and downside, the air deflector is
required as figure above (2).
SINAMICS V50 converter
9
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB