Technical data
● Continuous operation (green area in the figure)
Operating state that is permissible for the complete operating time.
● Short-time duty (yellow area in the figure)
Operating state that is permissible for less than 2% of the total operating time.
● Sporadic short-time duty (red area in the figure)
Operating state that is permissible for less than 1% of the total operating time.
9.5 Electromagnetic compatibility of the converter
EMC (electromagnetic compatibility) means that the devices function satisfactorily
without interfering with other devices and without being disrupted by other devices.
EMC applies when the emitted interference (emission level) and the interference
immunity are matched with each other.
The product standard IEC/EN 61800-3 describes the EMC requirements placed on
"Variable- speed drive systems".
A variable-speed drive system (or Power Drive System PDS) consists of the converter
as well as the associated electric motors and encoders including the connecting
cables.
The driven machine is not part of the drive system.
Note
PDS as component of machines or systems
When you install PDS into machines or systems, additional measures may be
required so that the product standards of these machines or systems is complied
with. The machine or system builder is responsible for taking these measures.
Overview of environments and categories
Environments
IEC/EN 61800-3 makes a distinction between the "first environment" and
"second environment" - and defines different requirements for these
environments.
● First environment
Residential buildings or locations at which the PDS is directly connected to a
public low- voltage supply without intermediate transformer.
● Second environment
An environment that includes all other establishments which are not
connected directly to a public low-voltage line supply.
Categories
● Category C1
Power Drive System (PDS) of rated voltage less than 1000 V intended for use in
the first (residential) environment.
● Category C2
Power Drive System (PDS) of rated voltage less than 1000 V, which is neither a
plug-in device nor a movable device, and when used in the first environment,
is only intended to be installed and commissioned by a professional.
SINAMICS V50 converter
86