Download Print this page

Siemens SINAMICS V50 Operating Instructions Manual page 31

Advertisement

Parameter description
6.1 Start and stop control (F1)
Code
Description
F1.00
Start mode
F1.01
Start freq.
Start freq.
F1.02
hold time
DC brake
F1.03
current at
start
DC brake
F1.04
time at start
Acc./Dec.
F1.05
mode
Time of S-
F1.06
curve nitial
stage
Time of S-
F1.07
curve rising
stage
F1.08
Stop mode
DC brake
trigger
F1.09
frequency at
stop
DC brake
F1.10
waiting time
at stop
DC brake
F1.11
current at
stop
DC brake
F1.12
time at stop
SINAMICS V50 converter
30
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
Setting range
0: Start directly
1: DC injection
brake first and then
start at start freq.
2: Speed tracking
and start
0.10~60.00Hz
0.0~10.0s
0.0~100.0% rated
current
0.0~30.0s
0: Linear
1: S-curve
10.0 50.0% (Acc./ Dec.
time)
F1.06+F1.07<90%
10.0~80.0% (Acc./
Dec. time)
F1.06+F1.07<90%
0: Deceleration to
stop 1: Coast to stop
2: Deceleration +DC
braking
0.00 550.0Hz
0.00~10.00s
0.0~100.0% rated
current
0.0~30.0s
Default
Modify
0
о
0.50Hz
о
0.0s
о
0.00%
о
0.0s
о
0
о
30.00%
о
40.00%
о
0
X
0.00Hz
0
0.00s
0
0.00%
0
0.0s
0
Modbus
Address
0200H
0201H
0202H
0203H
0204H
0205H
0206H
0207H
0208H
0209H
020AH
020BH
020CH

Advertisement