Parameter description
6.C Protection and Fault Parameters
Code
Description
Overvoltage point
FC.07
for Acc./Dec.
suspend
Input phase loss
FC.08
detection
Input phase loss
FC.09
detection delay
time
Output phase loss
FC.10
detection
Terminal close
FC.11
fault detection
Fault auto reset
FC.12
times
Fault auto reset
FC.13
interval
Under-voltage
FC.14
fault treatment
FC.15
Fast current limit
Fast current limit
FC.16
time
SINAMICS V50 converter
60
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
Setting range
resistor
mounted)
1: Valid for
Acc/Dec.
2: Valid all the
time
110.0~150.0%
(Bus voltage)
1~100% (100%
correspond to
800V)
2~255s
0: Invalid
1: Valid
0: Invalid
1: Valid
0—10, "0" means
auto reset is
disabled. Only 3
faults have auto
reset function
0.1~20.0s/time
0: No treatment
1: Auto reset at
power recovery
2: Auto run at
power recovery
(Auto run time
interval is
F1.16)
50.0%~100.0%
(100% means this
function is
disabled.)
0.01~1.00s
Default
Modify
380V:140%
X
220V:120%
20%
X
10s
X
1
о
1
о
0
X
5.0s
X
0
о
Depends
о
on model
0.10s
о
Modbus
Address
0D07H
0D08H
0D09H
0D0AH
0D0BH
0D0CH
0D0DH
0D0EH
0D0FH
0D10H