Parameter description
6.8 PID Parameters
Code
Description
F8.21
Dormancy delay
Dormancy
F8.22
threshold
Awaken
F8.23
threshold
PID feedback
F8.24
offline detection
range
PID feedback
F8.25
offline detection
time
PID feedback
F8.26
offline detection
Min. Freq.
6.9 Multi-step speed and PLC
Code
Description
Multi-step
F9.00
freq.1
Multi-step
F9.01
freq.2
Multi-step
F9.02
freq.3
Multi-step
F9.03
freq.4
Multi-step
F9.04
freq.5
Multi-step
F9.05
freq.6
SINAMICS V50 converter
54
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
Setting range
0~999s
0.0 320.0Hz
0.0~100.0%
(relative to pre-set
value)
0.0~100.0%
(relative to feedback
measuring range,
0.0% no detection)
0.0~50.0s
0.00~50.00Hz
Setting range
0.00 ~ Max
frequency
0.00 ~ Max
frequency
0.00 ~ Max
frequency
0.00 ~ Max
frequency
0.00 ~ Max
frequency
0.00 ~ Max
frequency
Default
Modify
120s
о
20.0Hz
о
80.00%
о
0.0%
о
2.0s
о
10.00Hz
о
Default
Modify
5.00 Hz
о
10.00 Hz
о
15.00 Hz
о
20.00 Hz
о
30.00 Hz
о
40.00 Hz
о
Modbus
Address
0915H
0916H
0917H
0918H
0919H
091AH
Modbus
Address
0A00H
0A01H
0A02H
0A03H
0A04H
0A05H

Advertisement