Technical data
Efficiency
Environment
9.2 Dimensions and weight
Dimensions drawing FSD...FSF
SINAMICS V50 converter
82
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
Used as rated power:
7.5kW and below ratings >93%,
11kW~45kW ratings >95%,
55kW and above ratings >98%
Application
Environment
Ambient
temperature
Humidity
Vibration
Altitude
Storage temperature -40~ +70°C
Indoor, free from sunshining directly,
dust, corrosive gas, combustible gas,
oil mist, steam, water drop or salt
-10 ~ +40°C, derated at 40 ~ 50°C, the
rated output current shall be decreased
by 1% for every temperature rise of 1°C
5~95%, no condensing
3.5mm, 2~9Hz;
10 m/s
, 9~200Hz;
2
15 m/s
, 200~500Hz
2
0~2000m;
Derating use above 1000m; Derate 1%
every 100m higher.