Technical data
● Category C3
Power Drive System (PDS) of rated voltage less than 1000 V intended for use in
the second (industrial) environment and not intended for use within the first
(residential) environment.
Second environment - category C3
Interference immunity
The converters with integrated line filters have been tested in accordance with
the immunity requirements of category C3, second environment, and fulfill the
requirements according to EN 61800-3.
Emitted interference
The converters comply with the limit values of the second environment,
category C3 when the following conditions are satisfied:
● EMC-compliant installation and configuration by qualified technician
● Operation on TN or TT line supply with star-point grounded
● Permissible motor cable length
● Shielded motor cable with low capacitance
● Pulse frequency restrictions:
– FSA ... FSG: Pulse frequency ≤ factory setting
– FSH/FSJ: pulse frequency ≤ 2 Hz
● With line filter (external or internal)
– The converters FSA ... FSJ with integrated line filters are suitable for
operation in the second environment, Category C3.
– The unfiltered converters FSA ... FSC with external line filters are suitable
for operation in the second environment, Category C3.
– The unfiltered converters FSD ... FSG with external line filters are suitable
for operation in the second environment, Category C3.
● With line reactor for FSH/FSJ
WARNING
Use the device in the second environment
This device is designed for operation in the second (industrial) environment
and may not be used in the first (residential) environment unless the
appropriate noise suppression measures have been adopted.
Note
Fault of the wireless services caused by high-frequency faults in
residential environments
This product can cause high-frequency interferences in a residential
environment that can require radio interference suppression measures.
● Have the installation and commissioning with appropriate radio interference
suppression measures performed by qualified personnel.