Download Print this page

Siemens SINAMICS V50 Operating Instructions Manual page 47

Advertisement

Parameter description
6.6 Input terminals
Code
Description
AI2 Max. input
F6.19
corresponding
setup
AI2 input filter
F6.20
time
PULSE Min.
F6.21
input
PULSE Min.
input
F6.22
corresponding
setup
PULSE Max.
F6.23
input
PULSE Max.
input
F6.24
corresponding
setup
F6.25
Pulse filter time
Terminal
F6.26
up/down initial
increment
Freq. ref.2
F6.27
datum
Delay duration
F6.28
of X1 terminal
close
Delay duration
F6.29
of X1 terminal
open
Delay duration
F6.30
of X2 terminal
close
Delay duration
F6.31
of X2 terminal
open
Pos. and Neg.
F6.32
logic terminal
X 1
SINAMICS V50 converter
46
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
Setting range
-200.0~200.0%
0.01~50.00s
0.00~F6.23
-200.0%~200.0%
F6.21~50.00kHz
-200.0%~200.0%
0.01~50.00s
0.00~10.00Hz
0: Max. freq.
1: Freq. ref.1
0.0~100.0s
0.0~100.0s
0.0~100.0s
0.0~100.0s
Pos. logic of Xi
terminal:
Be valid while
connecting between Xi
and COM.
Default
Modify
100.00%
о
0.05s
о
0.00kHz
о
0.00%
о
50.00kHz
о
100.00%
о
0.05s
о
0.01Hz
о
0
о
0.0s
о
0.0s
о
0.0s
о
0.0s
о
0000
X
Modbus
Address
0713H
0714H
0715H
0716H
0717H
0718H
0719H
071AH
071BH
071CH
071DH
071EH
071FH
0720H