Voltage Output Characteristics - Mitsubishi Electric AJ65VBTCU-68DAVN User Manual

Programmable controller digital-analog converter module
Hide thumbs Also See for AJ65VBTCU-68DAVN:
Table of Contents

Advertisement

3 SPECIFICATION

3.3.1 Voltage output characteristics

Number
Analog output Range Setting
1)
2)
3)
User range setting 1
User range setting 2
3 - 4
The voltage output characteristic graph is shown below.
10
5
0
-5
-10
-4096
-4000
-2000
Offset value
-10 to 10v
0 to 5V
1 to 5V
(-10 to 10v)
(0 to 5v)
Fig. 3.1 Voltage Output Characteristic
POINT
(1) Within the digital input and analog output scopes of each output range, the
maximum resolution and accuracy are within the performance specification
range. Outside those scopes, however, they may not fall within the performance
specification range. (Avoid using the dotted line part in Fig. 3.1.)
(2) Set the offset and gain values of the user range setting within the range
satisfying the following conditions.
(a) Setting range when user range setting 1 is selected: -10 to 10V
(b) Setting range when user range setting 2 is selected: 0 to 5V
(c) (Gain value) > (Offset value)
If you attempt to make setting outside the setting range of (a) or (b), the "RUN"
LED flickers at 0.5s intervals.
Set the values within the setting range.
If you attempt to make setting outside the setting range of (c), the "RUN" LED
flickers at 0.5s intervals.
Make setting again.
3
1
0
2000
Digital input value
Gain value
Digital Input value
0V
10V
0V
5V
1V
5V
0V
10V
0V
5V
1
2
4000
4095
Maximum resolution
-4000 to 4000
1.25mV
0 to 4000
-4000 to 4000
0 to 4000
MELSEC-A
2.5mV
1.0mV
2.5mV
1.0mV
3 - 4

Advertisement

Table of Contents
loading

Table of Contents