Programming; Programming Procedure - Mitsubishi Electric AJ65VBTCU-68DAVN User Manual

Programmable controller digital-analog converter module
Hide thumbs Also See for AJ65VBTCU-68DAVN:
Table of Contents

Advertisement

5 PROGRAMMING

5 PROGRAMMING
The programming procedure, basic read/write programs, and program examples for
the AJ65VBTCU-68DAVN are described.
When utilizing the program example introduced in this chapter for an actual system,
fully verify that there are no problems in controllability in the target system.
Refer to the user's manual of the master module used for the master module, to
Section 3.6 for the remote registers, and to the AnSHCPU/AnACPU/AnUCPU/QCPU
(A mode) Programming Manual (Dedicated Instructions) for details of the dedicated
instructions.

5.1 Programming Procedure

Create programs for executing the digital-analog conversion of the AJ65VBTCU-
68DAVN in the following procedure.
5 - 1
START
Analog output enable/disable setting
(D/A conversion enable/disable setting)
Output range setting
HOLD/CLEAR setting
Digital value setting
Analog output enable/disable specification
COMPLETION
1 When using the QCPU (Q mode), you can use the remote device station
initialization procedure registration function to make settings. When using the
ACPU, QCPU (A mode) or QnACPU, use the sequence program to make settings.
2 The remote device station initialization procedure registration function cannot be
used to make settings.
Use the sequence program to make settings.
MELSEC-A
1
Initial settings
2
2
5
5 - 1