5 PROGRAMMING
5 - 9
(2)
When using the program enclosed by the dotted line 1) in combination with
other remote device stations, correct the program as shown below.
[System configuration]
[Corrected program]
Note that the master module can register the initialization procedure of only
the specified station out of the multiple remote device stations.
The master module supporting this function is the QJ61BT11N which serial
No's first 5 digits is 08032 or later.
For details, refer to the CC-Link System Master/Local Module User's
Manual.
*2 Before the communication program is executed with remote device stations, the
program enclosed by the dotted line 1) enables the initial setting by using the
SB0D (remote device station initialization procedure registration instruction) and
SB5F (completion status of remote device station initialization procedure).
Initialization processing can't be made only by the parameter setting of GX
Developer.
*3 The program enclosed by the dotted line 2) is necessary only when the initial
settings are changed.
MELSEC-A
5 - 9