4 SETUP AND PREPARATION BEFORE OPERATION
(From the previous page)
Metal contacts
[Correct example]
[Wrong example]
(To the next page)
4 - 19
4) Set the plug cover.
5) Press the center part of the plug cover.
Pliers
6) Press both ends of the plug cover
Pliers
Latches
7) Check the press-fit condition (viewing from the wiring side).
After inserting the cable, put down the plug cover so that its
face is horizontal to the plug surface, allowing the metal
contacts to be fitted into the plug cover.
Using pliers, press the center part of the plug cover vertically
and strongly.
For the one-touch connectors, use adjustable pliers so that their
jaws can be widely opened.
After pressing the center part of the plug cover, press both ends
of the plug cover where latches are located.
Verify that the latches engage with the plug body.
Viewing from the wiring side, check that the plug surface is
flush with the plug cover.
Do not allow the plug cover to protrude from the plug surface.
Note: The condition where the plug cover is tilted or protrudes
from the plug surface as shown in [Wrong example] is an
improper press-fit condition.
Press the plug cover firmly with pliers until it looks like
[Correct example] condition illustrated on the left.