3 SPECIFICATION
3.6.4 CH.
output range setting (Address RWwm+9
RWwm+9
RWwm+A
3.6.5 HOLD/CLEAR setting (Address RWwm+B
3 - 17
(1) Set the analog output range per channel.
(2) Operation is performed according to the setting made for the leading edges of
initial data setting request flag (RY(n+9)).
(3) The default settings are -10 to 10V for all channels.
b15
to
b12
CH.4
b15
to
b12
CH.8
Output range
-10 to 10V
User range setting 1 (-10 to 10V)
User range setting 2 (0 to 5V)
POINT
If the set value is outside the setting range, error "20
flickers at intervals of 0.1s, and all channels do not make D/A conversion.
(1) Set HOLD/CLEAR to each channel.
(2) Operation is performed according to the setting made for the leading edges of
initial data setting request flag (RY(n+9)).
(3) The default settings are CLERA for all channels.
b15
b14
b13
b12
Ignored
, RWwm+A
H
b11
to
b8
CH.3
b11
to
b8
CH.7
0 to 5V
1 to 5V
indicates the channel No. where the error occurred.
)
H
b11
b10
b9
b8
)
H
b7
to
b4
b3
CH.2
b7
to
b4
b3
CH.6
Seting value
0
H
1
H
2
H
3
H
4
H
" occurs, the "RUN" LED
b7
b6
b5
b4
b3
CH.8 CH.7
CH.6 CH.5
CH.4 CH.3
MELSEC-A
to
b0
CH.1
to
b0
CH.5
b2
b1
b0
CH.2 CH.1
0: CLEAR
1: HOLD
3 - 17