Configuring H-Cpus With Profinet Rings And R1 Devices - Siemens SIMATIC S7-1500 System Manual

Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Summary of settings in STEP 7 and rules
Table 8-1  Setting of the MRP roles in STEP 7 and rules
Property
PROFINET ring
Topology
S7-1500R
possible in
redundant
system
MRP role of the
Manager
CPU
(auto)
MRP role of the
Client
IO devices
MRP role of
Client
devices outside
STEP 7 project
Rules
-
Reference
You can find information on the PROFINET topologies of S7-1500R/H redundant systems in
the PROFINET Function Manual.
(https://support.industry.siemens.com/cs/ww/en/view/49948856)
8.4

Configuring H-CPUs with PROFINET rings and R1 devices

Introduction
The section below guides you step by step through the configuration of PROFINET rings with
R1 devices for an S7-1500H redundant system. The configuration example consists of two R1
devices (ET 200SP IM 155-6 PN R1).
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD
Line topology
S7-1500H
S7-1500H
Manager
Not device in the ring
(auto)
Client
Not device in the
ring
Client
Not device in the ring
Assign individual R1 devices:
Assign in the network view: You have to connect
the left interface module of the R1 device to the H-
CPU with redundancy ID 1. You have to connect the
right interface module of the R1 device to the H-
CPU with redundancy ID 2.
Assign multiple R1 devices simultaneously:
1. In the network view, select the R1 devices.
2. Open the shortcut menu via the right mouse
button and select the menu command "Assign
new DP master/IO controller".
3. Select the two IO controllers (H-CPUs) in the
dialog.
Result: All marked R1 devices are assigned to the H-
CPUs
IMs on slot 0 with H-CPU with redundancy ID 1
IMs on slot 1 with H-CPU with redundancy ID 2
8.4 Configuring H-CPUs with PROFINET rings and R1 devices
Combined topo­
H-CPUs without additional devices
logy
S7-1500H
Not device in the ring
Depending on the
-
installation loca­
tion: Not device in
the ring or client
-
Configuration
Do not configure any further IO
devices in the STEP 7 project.
Do not connect PROFINET lines to the
PROFINET interfaces X1 P1R/X1 P2R of
the H-CPUs in the hardware configura­
tion.
203