Commissioning

11.8 Identification and maintenance data

Solution
1. Select the first R/H CPU in STEP 7.
2. Navigate to "Properties > General > Time" in the properties of the CPU.
3. Set the "Set NTP server in project" value at the "Time synchronization" parameter.
4. At "NTP Server 1:", enter the IP address of the NTP server: 192.168.1.15.
Figure 11-14  Example: Configuring the NTP server
5. Repeat steps 2 and 4 for the second CPU.
6. Download the hardware configuration to the primary CPU.
Result
The S7-1500R/H redundant system synchronizes its time with NTP server 192.168.1.15.
11.8
Identification and maintenance data
11.8.1
Reading out and entering I&M data
I&M data
Identification and maintenance data (I&M data) is information saved on the module. The data
is:
• Read-only (I data) or
• Read/write (M data)
Identification data (I&M0): Manufacturer information about the module that can only be
read. Some identification data is also printed on the housing of the module, for example
article number and serial number.
Maintenance data (I&M1, 2, 3): Plant-specific information, for example installation location.
Maintenance data for S7‑1500R/H is created during configuration and downloaded to the
redundant system.
S7‑1500R/H supports identification data I&M0 to I&M3. Exception: The synchronization
modules for S7-1500H only support identification data I&M0.
304
S7-1500R/H redundant system
System Manual, 11/2022, A5E41814787-AD